Well pressure tank size calculator
This calculator sizes a precharged well or booster pressure tank from pump flow, how long the pump should run, and the pressure-switch settings. Required drawdown is pump gallons per minute times that run time. Minimum tank volume is the drawdown divided by the Boyle's-law acceptance factor for the cut-in, cut-out, and precharge. A table gives that factor at 20/40, 30/50, and 40/60.
The arithmetic runs in your browser. The entries are not sent to a server to be calculated. The result is a volume in gallons. The page does not name a tank. For background on how well pressure tanks work, how precharge affects drawdown, and how tanks fail, read the well pressure tank guide. For how cut-in and cut-out pressures are set and adjusted, see the well pressure switch guide.
How the numbers are calculated
A precharged bladder or diaphragm tank starts full of air at the precharge pressure. As water enters, that air is compressed. Boyle's law says absolute pressure times air volume stays constant when the temperature stays constant. Absolute pressure here is gauge PSI plus 14.7, which is standard sea-level atmosphere. The usable water between cut-in and cut-out is:
Drawdown gallons = pump GPM × run time in minutes
Drawdown per gallon = (precharge + 14.7) × (1 / (cut-in + 14.7) − 1 / (cut-out + 14.7))
Minimum tank gallons = drawdown gallons / drawdown per gallon
When the precharge equals the cut-in pressure, the factor simplifies to (cut-out − cut-in) / (cut-out + 14.7). For a 30/50 switch that is 20 / 64.7 = 0.309. For 40/60 it is 20 / 74.7 = 0.268. For 20/40 it is 20 / 54.7 = 0.366.
Run time starts at 1 minute. Franklin Electric's AIM manual says a submersible motor should run a minimum of one minute so the start heat can leave the motor. If you enter horsepower, the run-time field becomes 1 minute per horsepower and stays at least 1 minute. That per-horsepower step is a planning allowance on this page. Amtrol's card uses 1 minute up to 3/4 HP and 2 minutes above 3/4 HP. Type the minutes your pump maker prints when you have them.
Drawdown per gallon at the standard settings
Multiply a tank's total gallons by the factor. The "precharge equals cut-in" column is the one that reproduces Amtrol's printed drawdown, rounded to 0.1 gallon. A 20-gallon tank at 30/50 with precharge equal to cut-in draws down 6.2 gallons on that card (MC7025, 03/26). The "2 PSI below" column is the usual air charge, set with the tank empty of water. Two small cells on the card print 0.1 gallon higher than this rounding: the 2-gallon model at 40/60, and the 14-gallon models at 40/60. The other cells checked against the card match.
| Switch | Precharge equals cut-in | Precharge 2 PSI below cut-in |
|---|---|---|
| 20/40 (20/40 PSI) | 0.366 | 0.345 |
| 30/50 (30/50 PSI) | 0.309 | 0.295 |
| 40/60 (40/60 PSI) | 0.268 | 0.258 |
Worked example
A 10 GPM pump that should run 1 minute needs 10 × 1 = 10 gallons of drawdown. On a 40/60 switch with a 38 PSI precharge, the absolute pressures are 52.7, 54.7, and 74.7 PSI. The factor is 52.7 × (1 / 54.7 − 1 / 74.7) = 0.258. Minimum total volume is 10 / 0.258 = 38.8 gallons. The displayed factor is rounded to three decimals; the volume uses the full factor and is then rounded to 0.1 gallon.
Pump flow can come from the well pump and booster size calculator. Use the flow the pump delivers inside the switch range when you have it.
Assumptions and limits
- The tank is a precharged bladder or diaphragm tank. A plain steel tank that keeps a free air charge over the water is a different device.
- Temperature is treated as constant. A hot mechanical room changes the real drawdown.
- 14.7 PSI is sea-level atmosphere. At higher elevation the absolute pressures are lower and the factor changes.
- Precharge above the cut-in is rejected. Precharge equal to cut-in is allowed, and the result says so, because that is the assumption behind the printed chart column.
- The usual charge is 2 PSI under the cut-in, read with the water drained out. A gauge on a tank that still holds water is reading water pressure, not the air charge.
- Drawdown here is for pump run time. It is not a reserve for a slow-recovering well.
- Accepted ranges stop at 200 GPM, 30 minutes, and 150 PSI cut-out.
When to call a pro
- You are about to drain a tank or set an air charge, and you are not sure the pump circuit is off.
- The pump is a variable-speed constant-pressure unit. Those tanks are sized by the drive maker, not by this on/off switch formula. Franklin's manual points that case to the drive manufacturer.
- The tank's working-pressure rating may be under the cut-out you entered. The Amtrol card lists 150 psig as the maximum for the models on its drawdown table. This page does not know the rating of the tank you have.
- Horsepower is large, or the maker asks for a longer run than the minutes you entered.
- The well recovers slowly and you need storage, not only a minimum run time.
- The house is well above sea level, or the tank is an older air-over-water tank.
Published tank specs are in the pump finder, with the pressure-tank use case selected.
Sources
- Amtrol Well-X-Trol specifications card MC7025 (03/26). Drawdown gallons at 30/50, 40/60, and 50/70, and the 1-minute / 2-minute run-time split on the quick-sizing table. Retrieved 2026-11-24.
- Franklin Electric AIM Manual, 60 Hz submersible systems. "Run motors a minimum of one minute to dissipate heat build up from starting current." Retrieved 2026-11-24.
- Engineering Toolbox, air pressure at altitude. Standard sea-level atmosphere is 14.696 PSI, used here as 14.7. Retrieved 2026-11-24.